Ausstellung in Ontario, Kalifornien · Support am Zielort anfragen
Startseite / Maschinen / Reindampferzeuger / Reindampferzeuger
SED-500CZQ-J
Auf Anfrage
SED-500CZQ-J
SED · SED-500CZQ-J · Hervorgehoben

SED-500CZQ-J — Reindampferzeuger

Die vollständige Beschreibung dieses Modells wird noch übersetzt. Lesen Sie die englischen Details oder fragen Sie unser Team nach weiteren Informationen. English

SED-500CZQ-J Pure Steam Generator. 500 kg/h sanitary pure-steam output for pharmaceutical equipment SIP. Vertical shell-and-tube design with double tube-sheet evaporator, pre-heater and recondenser per GB 150/GB 151. Wet

Lieferzeit
Auf Anfrage
Durchsatz
Kontaktieren Sie uns

Funktionsweise

Feed water enters via the Grundfos CRN1-7 (316) feed pump (with Schneider VFD), passes the pre-heater and is evaporated in the double-tube-sheet evaporator. The double-tube-sheet construction prevents primary-steam contamination of the pure-steam stream. Generated pure steam is condensed in a recondenser for sampling — its conductivity (Bürkert 8619 + 8221S, 0.055-20 μS/cm) and temperature (PT100) are monitored continuously. Plant steam is regulated through a GEMU/Bürkert pneumatic PID valve and trapped via Spirax Sarco. PLC + HMI manage all automation; a 6-channel paper recorder logs pressures/temperatures.

Prozessbeschreibung
1Feed water enters via the Grundfos CRN1-7 (316) feed pump (with Schneider VFD), passes the pre-heater and is evaporated in the double-tube-sheet evaporator.
2The double-tube-sheet construction prevents primary-steam contamination of the pure-steam stream.
3Generated pure steam is condensed in a recondenser for sampling — its conductivity (Bürkert 8619 + 8221S, 0.055-20 μS/cm) and temperature (PT100) are monitored continuously.
4Plant steam is regulated through a GEMU/Bürkert pneumatic PID valve and trapped via Spirax Sarco.
5PLC + HMI manage all automation; a 6-channel paper recorder logs pressures/temperatures.

Technische Daten

Technische Daten für Variante: SED-500CZQ-J

Technische Daten

Modell
SED-500CZQ-J
Versorgung
Plant steam (industrial steam) up to 0.6 MPa; purified water as feed; cooling water; compressed air 5.5-7.0 bar (filtered) for pneumatics; 380V/220V power
Konformitätsangaben
Pressure-vessel code: GB 150 / GB 151; design pressure 0.66 MPa; max working pressure 0.6 MPa; max working temperature 165 °C; FAT + IQ/OQ validation documentation included as standard
Luftdruck
Compressed air 5.5-7.0 bar (CA) for pneumatic actuators; design steam pressure 0.66 MPa, max working 0.6 MPa

Werkstoffe

Kontaktwerkstoffe
316L stainless steel (evaporator double tube-sheet, pre-heater, recondenser, all pure-steam wetted piping/valves/instruments, sanitary fittings); PTFE / EPDM (valve seals); silicone rubber (manhole gaskets)
Gehäusewerkstoffe
304 stainless steel (insulation jacket, support frame, control cabinet); composite silicate needle-felt (insulation material)

Wesentliche Merkmale

500 kg/h pure-steam output
Double tube-sheet vertical shell-and-tube evaporator (GB 150/151)
Wetted parts in 316L; 304 insulation jacket; composite silicate needle-felt insulation
Pre-heater + evaporator + recondenser package
Design pressure 0.66 MPa; max working pressure 0.6 MPa; max temperature 165 °C
Grundfos 316 stainless feed pump (CRN1-7, 0.37 kW) with Schneider VFD
Siemens or Schneider PLC + 10" color HMI
Hangzhou Meacon 6-channel paper-chart recorder
Bürkert online conductivity (8619 + 8221S electrode 0.055-20 μS/cm)
Diligen 316L PT100 temperature transmitters and pressure transmitters
Pneumatic actuation via AirTAC pilot solenoid + Bürkert/GEMU PID valves
DONJOY sanitary tri-clamp piping, valves and fittings
Spirax Sarco steam trap on plant-steam condensate
Premium imported components: Grundfos pumps, Schneider/Siemens controls, Bürkert conductivity, GEMU/Bürkert pneumatic PID valves, Spirax Sarco steam trap
Double tube-sheet design eliminates plant-steam cross-contamination
Tamper-proof paper recorder and online conductivity monitoring — regulatory ready
Manufactured to Chinese pressure-vessel codes GB 150 and GB 151
Sanitary tri-clamp connections throughout; full SIP/CIP compatibility

Anwendungen

Pure-steam generation for SIP of bioreactors, lyophilizers, autoclaves
Pure-steam supply on injectable / sterile manufacturing lines
Plant-wide pharmaceutical pure-steam loop

Branchen

Pharmaceutical / sterile manufacturing
Biotechnologie
Life sciences

Komponentenhersteller

Feed pump CRN1-7, 0.37 kW
Grundfos
VFD 0.37 kW
Schneider
Plant-steam pneumatic PID valve
GEMU / Bürkert
Steam trap (plant-steam condensate, ≤2000 kg/h)
Spirax Sarco
PLC
Siemens (S7-200 SMART) / Schneider (TM241)
HMI touchscreen 10" color
Siemens (SMART1000IE) / Schneider (GXU5512)
6-channel paper recorder R1006
Hangzhou Meacon
Pure-steam conductivity meter 8619
Bürkert
Pure-steam conductivity electrode 8221S (0.055-20 μS/cm)
Bürkert
Pure-steam temperature transmitter PT100 (sanitary)
Diligen
Pure-steam pressure transmitter 0-0.6 MPa
Diligen
Pneumatic angle/diaphragm/ball valves & sanitary fittings
DONJOY
Pilot solenoid valves and pressure regulator
AirTAC
Compressed-air pressure controller JC210
Korea 3S
Y-strainer / safety valves
Shanghai
Plant-steam pressure transmitter 0-0.6 MPa
Hangzhou Judong
Pressure gauges sanitary 0-0.6 MPa
Shanghai Zhiyan
Metal-tube flow meter (feed water 250-2500 L/h)
CSE
Evaporator level switch L2lS-1755
Shanghai Saiyuan
Control cabinet ECC
SS304 enclosure, low-voltage gear by Schneider
SED
Sprechen Sie mit SED Sales Team
Maschinenspezialisten · Kontakt per WhatsApp
Geschäftszeiten und Verfügbarkeit beim Team erfragen

Dokumentation

Datenblatt (PDF)
Überblick, technische Daten und Abmessungen · Originaldokument (Englisch)
Beim Vertrieb anfragen
Bedienhandbuch
Einrichtung, Betrieb und Fehlersuche · Originaldokument (Englisch)
Beim Vertrieb anfragen
Vergleichsdatenblatt (Standard und Economy)
Vergleich der Konfigurationen · Originaldokument (Englisch)
Beim Vertrieb anfragen
IQ / OQ / PQ-Protokolle
Validierungsunterlagen zur GMP-Konformität · Originaldokument (Englisch)
Beim Vertrieb anfragen
FAT / SAT-Protokolle
Abnahmeprüfungen im Werk und vor Ort · Originaldokument (Englisch)
Beim Vertrieb anfragen
CAD-Zeichnungen (STEP / IGES / DWG)
Konstruktionszeichnungen für die Aufstellung · Originaldokument (Englisch)
Beim Vertrieb anfragen
Kalibrierzertifikate
Schallpegel, Erdungswiderstand, Spannungsfestigkeit und Rauheit · Originaldokument (Englisch)
Beim Vertrieb anfragen
DQ (Designqualifizierung)
Vollständiges Designqualifizierungsprotokoll · Originaldokument (Englisch)
Beim Vertrieb anfragen
Werkstoffzeugnisse
Zusammensetzung des Edelstahls 316L · Originaldokument (Englisch)
Beim Vertrieb anfragen
SED
WhatsApp · SED Vertrieb
Vertriebskontakt · WhatsApp
→