Showroom em Ontario, Califórnia · Consulte o suporte para seu destino
Início / Equipamentos / Transformador trifásico a seco / Three-Phase Isolation Transformer (Y/Y, 30 kVA)
SED-30SGB-C
Consultar
SED-30SGB-C
SED · SED-30SGB-C · Em destaque

SED-30SGB-C — Three-Phase Isolation Transformer

A descrição completa deste modelo ainda está sendo traduzida. Consulte os detalhes em inglês ou solicite informações à nossa equipe. English

SED-30SGB-C 30 kVA Three-phase Isolation Transformer (Y/Y connection). Steps 480V three-phase down to 220V three-phase with neutral and PE. Rated current 78.7 A. Short-circuit impedance 4%, no-load current <=3%, output a

VDE0550IEC439JB5555GB226
Prazo de entrega
Consultar
Capacidade de produção
Fale conosco

Como funciona

Y/Y-connected three-phase isolation transformer with primary winding for 480V and secondary winding for 220V N PE. Magnetic isolation between input and output blocks DC, common-mode noise, and ground-loop currents. Class H insulation handles coil temperatures up to 155 deg C; dry-type air-cooling via cabinet ventilation louvers.

Processo de funcionamento
1Y/Y-connected three-phase isolation transformer with primary winding for 480V and secondary winding for 220V N PE.
2Magnetic isolation between input and output blocks DC, common-mode noise, and ground-loop currents.
3Class H insulation handles coil temperatures up to 155 deg C; dry-type air-cooling via cabinet ventilation louvers.

Especificações técnicas

Especificações da variante: SED-30SGB-C

Especificações

Modelo
SED-30SGB-C
Tensão
Input 480V 3P; Output 220V N PE 3P; rated current 78.7A; 50/60Hz
Detalhes de conformidade
Compliant with VDE0550, IEC439, JB5555, GB226 standards. Insulation resistance test instrument ZC25B-4 megohmmeter @ 1000V. Dielectric strength test instrument VG2670A withstand-voltage tester @ 20 mA.

Dimensões

Comprimento
580 mm
Largura
420 mm
Altura
630 mm
Peso
140 kg

Características principais

Three-phase isolation transformer, Y/Y connection
Capacity 30 kVA
Input 480V 3P; output 220V N PE 3P
Rated current 78.7 A; short-circuit impedance 4%; no-load current <=3%
Output accuracy +/-1%; voltage regulation <=1.5%; no waveform distortion
Class H insulation, coil insulation temp 155 deg C
Efficiency >=98%
1.2x rated load for 4 hours overload capability
Noise <=35 dB at 1 m; temperature rise <=60 deg C
Insulation resistance >=150 MOhm (measured >=50 MOhm at 1000V Megohmmeter)
Dielectric strength 3000 VAC / 1 min
Design life 20 years
Dry-type air-cooled
White metal cabinet with power meter, indicator lamps, ventilation louvers, casters
Internal three-column winding (A/B/C phase)
Galvanic isolation: protects sensitive equipment from upstream noise and ground loops
Compliant with VDE0550, IEC439, JB5555, GB226 standards
Industrial-grade construction with 20-year design life

Aplicações

Voltage matching of 480V mains to 220V three-phase loads
Galvanic isolation for sensitive electronics or instrumentation
Imported-equipment power conditioning (480/220V regions)
GMP plant utility transformer

Setores

Pharmaceutical / GMP plant utilities
Industrial machinery
Imported equipment installation
Power distribution
SED
Fale com SED Sales Team
Especialistas em equipamentos · contato pelo WhatsApp
Consulte o horário e a disponibilidade da equipe

Conformidade

VDE0550
IEC439
JB5555
GB226

Documentação

Ficha técnica (PDF)
Visão geral do equipamento, especificações e dimensões · Documento original (inglês)
Solicitar à equipe de vendas
Manual do operador
Instalação, operação e diagnóstico · Documento original (inglês)
Solicitar à equipe de vendas
Folha comparativa (Padrão e Econômica)
Comparação das configurações · Documento original (inglês)
Solicitar à equipe de vendas
Protocolos IQ / OQ / PQ
Documentação de validação para conformidade GMP · Documento original (inglês)
Solicitar à equipe de vendas
Protocolos FAT / SAT
Testes de aceitação na fábrica e no local · Documento original (inglês)
Solicitar à equipe de vendas
Desenhos CAD (STEP / IGES / DWG)
Desenhos de engenharia para a instalação · Documento original (inglês)
Solicitar à equipe de vendas
Certificados de calibração
Nível sonoro, resistência de terra, rigidez dielétrica e rugosidade · Documento original (inglês)
Solicitar à equipe de vendas
DQ (qualificação do projeto)
Protocolo completo de qualificação do projeto · Documento original (inglês)
Solicitar à equipe de vendas
Certificados de materiais
Composição do aço inoxidável 316L · Documento original (inglês)
Solicitar à equipe de vendas
SED
WhatsApp · Vendas SED
Contato comercial · WhatsApp
→